Engineering and remote access
3.8 OPC UA server
SITOP UPS1600 / UPS1100
172 Manual, 04.2017, A5E37775406-8-76
Display name
Data type
Definition
Description
AlarmUnknownBattery Boolean PropertyType Data from the battery cannot be read correctly. Battery is
defective or not supported by SIEMENS.
AlarmWrongBattery
Configuration
Boolean PropertyType Different battery types connected. Only batteries of the
same type can be operated together.
AlarmWrongBattery
Polarity
Boolean PropertyType Wrong battery polarity - check battery connections.
3.8.6.8
Battery
Display name
Data type
Definition
Description
BatteryCapacity
Setpoint
Float AnalogItemType Total battery capacity in Ah
BatteryDefectVoltage
Setpoint
Float AnalogItemType If battery voltage is lower than this value, the battery is con-
sidered defective
BatteryIgnoreCoding
Setpoint
Boolean PropertyType When this parameter is set to '1', data from the coded bat-
tery is ignored. The data is taken from the parameter as-
signment in this case.
3.8.6.9
Buffering
Display name
Data type
Definition
Description
BufferExpected
CurrentSetpoint
Float AnalogItemType Estimated average output current during buffer mode
BufferThreshold
Setpoint
Float PropertyType Trigger voltage for buffering - buffering is activated below
this value
BufferTime2Setpoint UInt16 AnalogItemType Additional buffer time after PC shutdown (valid only in con-
junction with SITOP UPS Manager)
BufferTimeSetpoint
UInt16
AnalogItemType
Desired buffering time before device switches off
BufferingEnableSet-
point
Boolean PropertyType Enable buffering
BufferingEndVoltage
Setpoint
Float AnalogItemType When battery voltage is lower than this voltage, the battery
charge is no longer sufficient. Buffering is stopped.
BufferingValid
SupplyVoltage
TimeSetpoint
Float AnalogItemType When the SITOP UPS1600 is in buffer mode, time for which
the input voltage must be OK again before SITOP UPS1600
buffering is stopped and connected devices are operated
again with input supply.

Table of Contents

Other manuals for Siemens SITOP UPS1600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SITOP UPS1600 and is the answer not in the manual?

Siemens SITOP UPS1600 Specifications

General IconGeneral
BrandSiemens
ModelSITOP UPS1600
CategoryPower Supply
LanguageEnglish

Related product manuals