4.21.6 - 3 heating zones, DHW, DHW return, solar, anti-legionella shu󰀪e pump and only one module switch to DHW
Figure 4-23 - Hydraulic connection
Settings:
Conguration > System >
Number of Modules 4
Module 1 Heating
Module 2 Heating
Module 3 Heating
Module 4 DHW
Outdoor sensor Yes
DHW Yes
DHW return sensor Yes
DHW Mode Sensor
Unit of measure °C
Number of Zones 3
Antilegionella Yes
Shu󰀪e type pump Antilegionella
Solar Yes
Solar Antistagnation Yes
Solar Antifrost Yes
Modbus enable No
Heat pump No
Conguration > Zones > 3 way valve > 3 way valve 1>
Zone Type Mix
Conguration > Zones > 3 way valve > 3 way valve 2>
Zone Type Mix
Conguration > Zones > 3 way valve > 3 way valve 3>
Zone Type Mix