TUTORBIT
COSMOGAS
4.22.1 - Water Heater with tank without coil, DHW and a DHW return zone
Figure 4-37 - Hydraulic connection
Settings:
Conguration > System >
Number of Modules 4
Module 1 Heating
Module 2 Heating
Module 3 Heating
Module 4 Heating
Outdoor sensor No
DHW Yes
DHW return sensor Yes
DHW Mode Sensor
Unit of measure °C
Number of Zones 1
Antilegionella Yes
Shu󰀪e type pump Absent
Solar No
Modbus enable No
Heat pump No
Conguration > Zones > 3 way valve > 3 way valve 1> Zone type No Mix
Parameters > DHW > Adjustement > Temp o󰀨set up = 0
Note: The sensor “47” has no function but must be connected.