67
TUTORBIT
COSMOGAS
6 - USE
Figure 6-1 - Main page
6.1 - Main page
When you switch on TutorBit, you automatically access the
home screen that shows the status of the system.
Figure 6-1 shows the main screen in its maximum conguration,
with the explanation of each row.
Information on the home screen Description of the contents
Cosmogas Srl 8/8
Cosmogas Srl = company name; 8/8 = Cursor position
DDD DD.MM.YYYY hh:mm:ss
DDD=Weekday; DD.MM.YYYY = Current date; hh:mm:ss = Current time
State 100% 100% 100% 100%
State of each module. There can be a maximum of 4. The state can display the following
values:
OFF = module off
Stb = module in stand by
1…100% = output range requested to the module, corresponding to the 0-10V signal
output from TutorBit.
Cascade S 70°C M 69°C
Cascade sensor state Water Heater T., where;
“S”= Setpoint;
“M”= Measured temperature.
1 OFF S 45°C M 44°C
Zone 1 state and setting, where:
ANF = Antifrost; Stb = stand-by; ON = heat demand; OFF = circuit off;
S = Setpoint temperature;
M = Measured temperature
2 OFF S 45°C M 44°C
Same meaning as Zone 1 but relative to Zone 2.
3 OFF S 45°C M 44°C
Same meaning as Zone 1 but relative to Zone 3.
4 OFF S 45°C M 44°C
Same meaning as Zone 1 but relative to Zone 4.
5 OFF S 45°C M 44°C
Same meaning as Zone 1 but relative to Zone 5.
DHW OFF M 10°C
DHW circuit state and setting, where: ANL = Anti-legionella; Stb = stand-by; ON = heat
demand; OFF = circuit off;
M = Temperature measured by the domestic hot water tank sensor.
Solar OFF M 100°C
Solar circuit state and setting, where: ANF = Antifrost; ASG = Anti-stagnation; Stb =
stand-by; ON = heat demand; OFF = circuit off;
M = Temperature measured by the solar panel sensor
HP OFF S 45°C M 44°C
Heat pump state and setting, where: Stb = stand-by; Heat = HP on Heating;
Cool = HP on cooling; DHW= HP on domestic hot water;
S = Required temperature;
M = Temperature measured by sensor Water Heater T.
NOTE: When HP = DHW, s = 0 and M= 0 because the values on the “DHW” line apply.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens TUTORbit POL945 and is the answer not in the manual?

Siemens TUTORbit POL945 Specifications

General IconGeneral
BrandSiemens
ModelTUTORbit POL945
CategoryController
LanguageEnglish

Related product manuals