05.2006 Parameterization
SIEMENS AG 6SE7087-2JD60
SIMOVERT MASTERDRIVES Operating Instructions 8-21
The following example shows the individual operator control steps to be
carried out on the PMU for a parameter reset to factory setting.
P
Ê Ì
P053
Ê Ì
Ê Ì
Set P053 to 0002 and grant parameter access for PMU
P
Ê Ì
0000 0001 0002 P053
Ê Ì
P053
Select P060
P060
P
Ê Ì
P060
Set P060 to 0002 and select "Fixed settings" menu
1
Ê Ì
P060
Select P970
P366
P
Ê Ì
P970
Set P970 to 0000 and start parameter reset
1
P
Ê Ì
2 P060
Ê Ì
Ê Ì
P970
P
Ê Ì
0 °009
Ê Ì
Example