Parameterizing Steps 05.2006
6SE7087-2JD60 Siemens AG
9-66 Operating Instructions SIMOVERT MASTERDRIVES
Only deviations from the standard setting (P114 = 0) are indicated:
P114 = 0 P114 = 1 P114 = 2 P114 = 3 P114 = 4 P114 = 5 P114 = 6 P114 = 7
P216=Smooth n/f(FWD)
0ms (n-ctrl.)
4ms (f-ctrl.)
4.8ms
(n-ctrl.)
P217=Slip Fail Corr'n. 0=off 2=on (n-ctrl) 2=on
P223=Smooth n/f(act)
4ms (n-ctrl.)
0ms (f-ctrl.)
100ms
P235=n/f-Reg Gain1 3.0 or 5.0 12.0 (n-ctrl.)
P236=n/f-Reg Gain2 3.0 or 5.0 12.0 (n-ctrl.)
P273=Smooth Isq(set) 6*P357 (T0) 3*P357
P240=n/f-Reg Tn 400ms 40ms (n-ctrl.)
P279=Torque (dynamic) 20.0% 80% (f-ctrl.)
P287=Smooth Vd(act) 9 0 0
P291=FSetp Flux(set) 100% 110%
P295=Efficiency Optim. 100%=off 99.9% 50%
P303=Smooth Flux(set) 10-20ms 60ms
100 (n-ctrl.)
500 (f-ctrl.)
P315=EMF Reg Gain Gain(n)
1.5*Gain(n)
(f-ctrl.)
1.5*Gain(n)
(f-ctrl.)
P339=ModSystRelease 0=All syst 3=only RZM 3=only RZM 3=only RZM 3=only RZM 3=only RZM
P344=ModDepthHeadrm 0.0% 3.0% 3.0% 30.0%
P536=n/f RegDyn(set) 50% 20%
100 (n-ctrl.)
50% (f-ctrl.)
200 (n-ctrl.)
100 (f-ctrl.)
200 (n-ctrl.)
50% (f-ctrl.)
25%
100 (n-ctrl.)
50% (f-ctrl.)
100% (n-ctrl.
RZM = Space vector modulation
The gain Kp of the speed controller (P235, P236) depends on the
inertia of the drive and has to be adapted if necessary.
Symmetrical optimum: P235 = 2 x P116 / P240
Kp = 2 x T
start-up
/ Tn
The start-up time is the time taken by the drive to accelerate to rated
speed when the rated torque is specified. This is determined during
automatic speed controller optimization.