05.2006 Technical Data
Siemens AG 6SE7087-2JD60
SIMOVERT MASTERDRIVES Operating Instructions 13-9
Designation Value
Order No. 6SE70... 14-5FB61 16-2FB61 17-8FB61 21-1FB61 21-5FB61 22-2FC61
Rated voltage [V]
• Input
• Output
3 AC 500 (- 15 %) to 600 (+ 10 %)
3 AC 0 up to rated input voltage
Rated frequency [Hz]
• Input
• Output: V/f = constant
V = constant
50 / 60 ± 6 %
0 to 600
8 to 300
Rated current [A]
• Input
• Output
5.0
4.5
6.8
6.2
8.6
7.8
12.1
11.0
16.6
15.1
24.2
22.0
DC link voltage [V] 675 (- 15 %) to 810 (+ 10 %)
Rated output [kVA] 3.9 to 4.6 5.4 to 6.4 6.8 to 8.1 9.6 to 11.4 13.1 to 15.6 19.1 to 22.8
Auxiliary current supply [V] DC 24 (20 - 30)
• Max. aux. curr. requirement[A]
Standard version at 20 V
1.5
• Max. aux. curr. requirement[A]
Maximum version at 20 V
2.5
Pulse frequency [kHz] 1.5 to 16 (see Fig. „Derating curves“)
Load class II to EN 60 146-1-1
Base load current [A] 0.91 x rated output current
Base load duration [s] 240
Overload current [A] 1.36 x rated output current
Overload duration [s] 60
Load class II to EN 60 146-1-1 (additional)
Base load current [A] 0.91 x rated output current
Base load duration [s] 270
Overload current [A] 1.6 x rated output current
Overload duration [s] 30
Losses, cooling, power factor
Power factor
• Line cosϕ1L
• Converter cosϕC
≥ 0.98
< 0.92 ind.
Efficiency η (rated operation) ≥ 0.97 ≥ 0.98
Power loss (at 2.5 kHz) [kW] 0.09 0.14 0.12 0.15 0.23 0.33
Cooling-air requirement [m³/s] 0.022 0.022 0.022 0.022 0.022 0.028
Pressure drop ∆p [Pa] 32 32 32 32 32 30
Sound pressure levels, types of construction, dimensions, weights
Sound pressure level [dB(A)] 60 60 60 60 60 60
Type of construction B B B B B C
Dimensions [mm]
• Width
• Height
• Depth
135
425
350
135
425
350
135
425
350
135
425
350
135
425
350
180
600
350
Weight approx. [kg] 12.5 12.5 12.5 12.5 12.5 21
Table 13-7 Air-cooled converter (part 5)