User Manual of A90 Series Inverter
216
7.13 Keyboard and Display Function Parameter Group of F12 Group
M.K
multi-function key
options
0: no function
1: forward jog
2: reverse jog
3: forward/reverse
switching
4: quick stop
5: free stop
6: cursor movement to the
left
is a multi-function key, of which the function can be performed by setting the
function code F12.00. If F12.00=0, this key has no effect when pressed. For other settings,
the corresponding effects will be obtained when this key is pressed.
Options of stop
function of STOP
key
0: valid only in keyboard
control
1: with all command channels
valid
According to the setting of the function code F00.02 (command source option), the
command sources are divided into the keyboard, terminal and communication. If the
terminal is selected as the current command source, the Run
and Stop
key
on the keyboard will be unavailable. In more dangerous cases, however, the fastest way is
to stop the inverter via the Stop
key on the keyboard to resolve dangers. It is the
most convenient to use the keyboard to stop the inverter during normal operation. Therefore,
the function code “F12.01: stop function options of the STOP key” is added. In addition,
the STOP key is always valid by default.
★
It is recommended not to modify this parameter. If necessary, please set it
carefully.
0: do not lock
1: reference input not locked
2: all locked, except for this