23. Appendix G: EX245-FPS Timing Values
Specific timing values of SMC EX245-FPS1/2/3
Input delay
: tFilter + 2 ms
tFilter = Parameterized filter time
Output delay
1
: 1 ms
WCDT in
: Input delay + 12 ms
WCDT out
: Output delay
1
+ 12 ms
One Fault delay time (OFDT) IN 1oo2
: WCDT in
One Fault delay time (OFDT) IN 1oo1
: 122 ms
One Fault delay time (OFDT) OUT M
: WCDT out
One Fault delay time
1
(OFDT) OUT Z1..3
: 30 ms
Device acknowledge time (DAT)
: 20 ms
For calculating/determining the response time (safety function response time – SFRT) please look at the
user manual of the used safe profinet controller.