- 48 -
No.EX##-OMY0004
9.2. Maintenance alarm for the Fibre-optic cables
When the signal strength margin of the Fibre-optic communication is not enough, the EX245-FPS1
issues a "Maintenance alarm" for the Fibre-optic cable, if monitor setting of communication port is
enabled.
If the FO LED of the EX245-FPS1 is flashing (more than 0 dB but less than 2 dB) or ON (the margin is 0
dB), refer to the Section 10.8.1.5.
In order to recover from this alarm, please check in the following order.
Example
Step 1: Check/exchange the Fibre-optic cable.
Step 2: Check/exchange the previous device.
Step 3: Check/exchange the EX245-FPS1.
EX245-FPS1
Port1
Port2
FO1: ON
Previous Device
Port
Next Device
Port
FO2: OFF