- 36 -
No.EX##-OMY0004
8.2. Parameterisation
8.2.1. PROFIsafe Parameters (F-Parameters)
Table 8-3 F-Parameter details
Parameter
Range
Default
Type of parameter
F_SIL
SIL3
SIL3
Static
F_Block_ID
0 to 7
1
Static
F_Par_Version
1
1
Static
F_Source_address
Automatic
1
Static
F_Destination_address
1 to 1023
1 (factory default setting)
Static
F_WD_Time
10 to 10,000 ms
150 ms
Static
F_iPar_CRC ()
More than 0
81F1628F
Static
() F_iPar_CRC is present only in mode: Safety Mode (Channel Passivation)
Refer to Section 18 for details of all F-parameters.
8.2.2. Module parameters
8.2.2.1. Module parameters for Valve zone 1 - 3
The Valve zone 1 - 3 has no module parameters that you can set.
8.2.2.2. Module parameters for EX245-DX1
The EX245-DX1 has no module parameters that you can set.
8.2.2.3. Module parameters for EX245-DY1
The EX245-DY1 has no module parameters that you can set.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks EX245-FPS1 and is the answer not in the manual?

SMC Networks EX245-FPS1 Specifications

General IconGeneral
BrandSMC Networks
ModelEX245-FPS1
CategoryControl Unit
LanguageEnglish

Related product manuals