No.EX##-OMY0004
4. General Specifications
Table 4-1 EX245 series general specifications
Item
Specification
Rated voltage
24 V DC +20% -15%
Supply interruption for no loss of function
1 ms maximum
Protection class
IP65 (when fully installed or fitted with protective cover)
(complies with IEC 60529)
Insulation resistance
10 Mohm @ 500 VAC between FE and all accessible terminals to
IEC 61131-2.
Withstand voltage
500 VAC for 1 min. between FE and all accessible terminals to IEC
61131-2
Ambient temperature
Operation: -10 °C to 50 °C
Storage: -20 °C to 60 °C
Ambient humidity
35% to 85% RH (non-condensing)
Atmospheric pressure
Operation: 80 kPa to 108 kPa (under 2000 m)
Storage: 66 kPa to 108 kPa (under 3500 m)
Vibration resistance
10 Hz to 57 Hz (constant amplitude) 0.75 mm
57 Hz to 150 Hz (constant acceleration) 49 m/s
2
2 hours in each direction X, Y and Z
Impact resistance
147 m/s
2
is applied 3 times in each direction X, Y and Z
EN 60068-2-27/29
Operating environment
No corrosive gas
EMC directive
Yes, 2014/30/EU, IEC61326-3-1
Machinery directive
Yes, 2006/42/EC, EN 62061, EN ISO 13849
TUV Certification
Yes, EN 61508, EN 62061, EN ISO 13849
PROFINET & PROFIsafe
Yes
UL
Yes, for used materials (UL508)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks EX245-FPS1 and is the answer not in the manual?

SMC Networks EX245-FPS1 Specifications

General IconGeneral
BrandSMC Networks
ModelEX245-FPS1
CategoryControl Unit
LanguageEnglish

Related product manuals