Pressure Setting
■Measurement mode
The measurement mode is the condition where the pressure is detected and displayed, and the switch
function is operating.
This is the basic mode, and other modes should be selected for setting changes and other function settings.
Operation
When the pressure exceeds a set value, the switch will be turned ON.
When the pressure falls below the set value by the amount of hysteresis or more, the switch will be turned
OFF.
The default setting of the output set value is the central value between the atmospheric pressure and the
upper limit of the rated pressure range.
If this condition, shown below, is acceptable, then keep these settings.