STATYS 200-1000A - Ref.:OPMSTA200910-GB_06
Automatic load resupply (System access)
Display: aut on (automatic on)
Use of automatic resupply
Display: aut on (automatic on)
Default value: no
Possible choice: yes or no
Delay before automatic resupply
Display: dly (delay)
Default value: 0 seconds
Possible choice: 0 to 65535 (if aut on = yes)
Automatic retransfer to the preferred source (System access)
Display: aut sb (automatic switchback)
Use of automatic switchback
Display: aut sb (automatic switchback)
Default value: no
Possible choice: yes or no
Delay before automatic switchback
Display: dly (delay)
Default value: 3 seconds
Possible choice: 0 to 65535 (if aut sb = yes)
Nominal voltage (System access)
1
Display: un (Un)
Default value: nominal value measured by the equipment
Possible choice: 100V to 499V
Nominal frequency (System access)
1
Display: fn (F)
Default value: nominal value measured by the equipment
Possible choice: 50 or 60 Hz
1
Values used to calculated upper and lower limits.