Never work alone when servicing this equipment. Two persons are
required until the inverter is properly shut down and verified de-energized
with a meter.
The
Emergency
stop button
will
shutdown
the
inverter (disconnects the AC
contactor and stops the IGBT matrix)
immediately
when
it
is
punched
(pressed down).
The inverter must be started up manually through LCD control menu if
users want to recover the operation after the button is punched.
Check “Start the inverter” of chapter 6 in the operation manual for details.
The
AC
circuit breaker
is
one of
the
primary
disconnects
for
the
inverter.
The
inverter's
doors cannot
be
opened
until
the
switch of the
AC
circuit breaker
is
in
the
OFF
position.
When
the
AC main
switch
is
in
the
OFF
position,
all
AC
power
is
disconnected
(not
live), except
the
following
areas:
•
The
input
side
of
the
AC circuit breaker (the utility grid)
•
The
DC
input terminals (if the PV array is connected and energized)
To
operate
the
inverter
the
AC
circuit breaker
switch
must
be
in
the
ON
position.
The
DC
circuit breaker
is
also th
e
primary
disconnect
for
the
inverter.
The
inverter's
doors cannot
be
opened
until
the
switch of the
DC
circuit
is
in
the
OFF
position.
When
the
DC main
switch
is
in
the
OFF
position,
all
DC
power
is
disconnected
(not
live), except
the
following
areas:
•
The
input
side
of
the
AC
main
switch (the utility grid)
•
The
DC
input terminals (if the PV array is connected and energized)
To
operate
the
inverter
the
DC
circuit breaker
switch
must
be
in
the
ON
position.