EasyManuals Logo
Home>Thytronic>Relays>NA10

Thytronic NA10 User Manual

Thytronic NA10
177 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #123 background imageLoading...
Page #123 background image
APPENDIX
123
NA10 - Manual - 04 - 2022
Residual overcurrent 50N/51N - Very inverse time curve (IEC 60255-3/BS142 type B)
F_51N-IECB-Char.ai
1.1
2 3 4 5 6 7 8 9 10 20
I
E
/I
E
>inv
0.01
0.1
1
10
100
1000
10000
t [s]
t
E>inv
= 10 s
t
E>inv
= 60 s
t
E>inv
= 5 s
t
E>inv
= 1 s
t
E>inv
= 0.5 s
t
E>inv
= 0.2 s
t
E>inv
= 0.02 s
t
E>inv
= 0.1 s
t =
t
E
>
inv
·
[(I
E
/I
E
>
inv
) -1]
13.5
Note: match of operating and setting time takes place when I
E
/I
E
>
inv
= 14.5

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Thytronic NA10 and is the answer not in the manual?

Thytronic NA10 Specifications

General IconGeneral
BrandThytronic
ModelNA10
CategoryRelays
LanguageEnglish

Related product manuals