EasyManuals Logo
Home>Thytronic>Relays>NA10

Thytronic NA10 User Manual

Thytronic NA10
177 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #124 background imageLoading...
Page #124 background image
APPENDIX
124
NA10 - Manual - 04 - 2022
Residual overcurrent 50N/51N - Extremely inverse time curve (IEC 60255-3/BS142 type C)
F_51-IECC-Char.ai
1.1
2 3 4 5 6 7 8 9 10 20
IE
/IE>inv
0.01
0.1
1
10
100
1000
10000
100000
t [s]
tE>
inv
= 10 s
tE>
inv
= 60 s
tE>
inv
= 5 s
tE>
inv
= 1 s
tE>
inv
= 0.5 stE>
inv
= 0.2 stE>
inv
= 0.02 s tE>
inv
= 0.1 s
t =
t
E
>
inv
·
[(I
E
/I
E
>
inv
)
2
-1]
80
Note: match of operating and setting time takes place when I
E
/I
E
>
inv
= 9