9 TROUBLESHOOTING
9-1. Overview
(1) Before engaging in troubleshooting
(a) Applicable models
All Super Heat Recovery Multi (SHRM-e) models.
(Indoor units: MM*-AP***, Outdoor units: MMY-MAP0726FT2P-UL )
(b) Tools and measuring devices required
(c) Screwdrivers (Philips, flat head), spanners, long-nose pliers, nipper, pin to push reset switch, etc.
(d) Multimeter, thermometer, pressure gauge, etc.
(c) Things to check prior to troubleshooting (behaviors listed below are normal)
(2) Troubleshooting procedure
When a problem occurs, proceed with troubleshooting in accordance with the procedure shown below.
NOTE
Rather than a product trouble (see the List of Check Codes below), the problem could have been caused by
a microprocessor malfunction attributable to a poor quality of the power source or an external noise. Check
for possible noise sources, and shield the remote controller wiring and signal wires as necessary.
esuac elbissoProivaheB.ON
1
A compressor would not start • Could it just be the 3-minute delay period (3 minutes after compressor
shutdown)?
•
Could it just be the air conditioner having gone thermostats OFF?
• Could it just be the air conditioner operating in fan mode or put on the timer?
• Could it just be the system going through initial communication?
2
An indoor fan would not start • Could it just be cold air discharge prevention control, which is part of
heating?
3
An outdoor fan would not start or would
change speed for no reason
• Could it just be cooling operation under low outside temperature
conditions?
• Could it just be defrosting operation?
4
An indoor fan would not stop • Could it just be the elimination of residual heat being performed as part of
the air conditioner shutdown process after heating operation?
5
The air conditioner would not respond to a
start/stop command from a remote controller
• Could it just be the air conditioner operation under external or remote
control?
Problem
Any other problem
Investigate check code
displayed on interface P.C. board
of header unit
Investigate check code
displayed on interface P.C.
board of relevant follower unit
Check the problem
site or problem part
"E28" check code
CAUTION
The cooling performance may decling considerably when total operating capacity of cooling indoor units
is less than 036 type while ambient temperature is below.
− 135 −