6-7. Applied control for Outdoor Unit
The outdoor fan high static pressure support and priority operation mode setting (cooling / heating / number of
units / or priority indoor unit) functions are made available by setting relevant switches provided on the
interface P.C. board of the outdoor unit.
6-7-1. Outdoor Fan High Static Pressure Shift
Purpose/characteristics
This function is used when connecting a duct to the discharge port of an outdoor unit (as part of, for example,
unit installation on the floor by floor installation.)
Setup
Turn ON the DIP switch [SW10, Bit 2] provided on the interface P.C. board of the outdoor unit.
This function must be enabled with every discharge duct connected outdoor unit for both of the header and
follower units.
Specification
Increase the speed of the propeller fan units on the outdoor fan to allow the installation of a duct with a
maximum external static pressure not greater than specified in the table below. If a discharge duct with a
resistance greater than 15 Pa (1.5 mmAq) is to be used, enable this function. The maximum external static
pressures of base units are shown below (Table 1). In the case of combined use of multiple outdoor units, set
all the units to the same maximum external static pressure as the one with the lowest maximum external static
pressure (see table2).
Table 1: Maximum External Static Pressures of Base Outdoor Units
Table 2: Maximum External Static Pressures for Combined Use of Base Units
(1) Standard models
Model MMY- MAP0804
MAP1004
MAP1204
MAP1404
Maximum external static pressure (Pa) 50 40 40 40
(*) Outdoor unit air flow
(*) Calculate duct resistance from outdoor unit air flow.
(m
3
/h) 8700 9420 12000 12960
Combined
horsepower output
Model
MMY
Combination of outdoor units
Unit 1
MAP0804
MAP1004
MAP1204
MAP1404
MAP0804
MAP1004
MAP1004
MAP1204
MAP1404
MAP1404
MAP1404
MAP1004
MAP1204
MAP1404
MAP1204
MAP1404
MAP1404
MAP1404
MAP0804
MAP1004
MAP1204
MAP1404
AP1614
AP1814
AP2014
AP2214
AP2414
AP2614
AP2814
AP3014
AP3214
AP3414
AP3614
AP3814
AP4014
AP4214
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
MAP0804
MAP0804
MAP1004
MAP1004
MAP1004
MAP1204
MAP1404
MAP1004
MAP1004
MAP1004
MAP1204
MAP1204
MAP1404
MAP1404
MAP1004
MAP1004
MAP1004
MAP1204
MAP1204
MAP1204
MAP1404
50
40
40
40
50
40
40
40
40
40
40
40
40
40
40
40
40
40
Unit 2 Unit 3
Maximum external
static pressure
(Pa)
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba MMY-MAP0804FT8(ZG)-E and is the answer not in the manual?

Toshiba MMY-MAP0804FT8(ZG)-E Specifications

General IconGeneral
BrandToshiba
ModelMMY-MAP0804FT8(ZG)-E
CategoryAir Conditioner
LanguageEnglish

Related product manuals