– 153 –
(1) Single cooling test operation function
This function is provided to change collectively the mode of all the indoor units connected to the same system
for the cooling test operation mode, by using switches on the interface P.C. board of the header unit.
<Operation procedure>
Power ON
Start
Operation check
[A]
[C. ]
[B]
[ – C]
Stop/End
Be sure to turn on power at the indoor side
before power-ON of outdoor unit.
Set SW01/SW02/SW03 on the interface P.C. board of the header unit
to [2/5/1]. ([C. ] is displayed on 7-segment display [A].)
[Test run] is displayed on the remote controller of
the indoor unit to be operated.
Check that [ – C] is displayed on 7-segment
display [B] on the interface P.C. board of the
header unit.
Push SW04 on the same board for 2 seconds or more.
Return SW01/SW02/SW03 on the interface P.C. board of the header
unit to [1/1/1],
or push the push switch SW05 for 2 seconds or more.
7-segment display [A] 7-segment display [B]
SW04 SW05
<Rotary switches>
SW02 SW03SW01
NOTE) The test operation returns to the normal operation after 60 minutes.
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk

Table of Contents

Questions and Answers:

Toshiba MMY-MAP0804FT8(ZG)-E Specifications

General IconGeneral
Energy Efficiency Ratio (EER)3.5
Weight (Indoor Unit)9.5 kg
Energy Efficiency Ratio (Cooling)3.5
Noise Level (Outdoor Unit)50 dB
Indoor Unit Weight9.5 kg

Related product manuals