Wireless remote controller
1 Turn on the power of the air conditioner.
When power is turned on for the first time
after installation, it takes approx. 5
minutes until the remote controller
becomes available. In the case of
subsequent power on, it takes approx. 1
minute until the remote controller
becomes available. Execute a test run
after the predetermined time has passed.
2 Push “ON/OFF” button on the remote
controller, select
[ Cool ] or [ Heat ]
with “MODE” button, and then select
[
HIGH ] with “FAN” button.
3
Cooling test run Heating test run
Set the temperature to 17°C
with the temp. setup buttons.
Set the temperature to 30°C
with the temp. setup buttons.
Cooling test run Heating test run
After confirming a signal
receiving sound “beep”
immediately set the
temperature to 18°C with the
temp. setup buttons.
After confirming a signal
receiving sound “beep”
immediately set the
temperature to 29°C with the
temp. setup buttons.
Cooling test run Heating test run
After confirming a signal
receiving sound “beep”
immediately set the
temperature to 17°C with the
temp. setup buttons.
After confirming a signal
receiving sound “beep”
immediately set the
temperature to 30°C with the
temp. setup buttons.
4
5
6
Repeat procedures 4
oo
oo
o
5
oo
oo
o
4
oo
oo
o
5.
Indicators “Operation” (green), “Timer”
(green), and “Ready” (orange) in the
wireless receiver section flash in approx.
10 seconds, and the air conditioner starts
operation. If any of these indicators does
not flash, repeat procedures 2 to 5.
7 Upon completion of the test run, push
“ON/OFF” button to stop operation.
<Overview of test run operations using the wireless
remote controller>
Cooling test run:
ON/OFF o 17°C o 18°C o 17°C o 18°C o 17°C
o18°C o 17°C o(test run) o ON/OFF
Heating test run:
ON/OFF o 30°C o 29°C o 30°C o 29°C o 30°C
o29°C o 30°C o(test run) o ON/OFF
Test operation from the outdoor unit
Refer to “7-7-2. Function to Start/Stop (ON/OFF)
Indoor Unit from Outdoor Unit” in “7-7. Service
Support Function.
Note: The test operation returns to normal operating
mode after 60 minutes.
- 142 -

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba MMY-MUP2001HT8P-A and is the answer not in the manual?

Toshiba MMY-MUP2001HT8P-A Specifications

General IconGeneral
BrandToshiba
ModelMMY-MUP2001HT8P-A
CategoryAir Conditioner
LanguageEnglish

Related product manuals