E6581288
− 10 
4.4.1. Input/Output signal
*The default value is 0(zero) of RY and RX.
(1) Output signal Master unit -> Inverter
The output signal from the master unit is shown. (The input signal to the inverter.)
Device No. Signal Description
RYn0 Forward run command
OFF: Stop command ON: Forward run command
RYn1 Reverse run command OFF: Stop command ON: Reverse run command
RYn2 Input terminal selection5(S1) The function depends on input terminal selection 5(f115). *2
RYn3 Input terminal selection6(S2) The function depends on input terminal selection 6(f116). *2
RYn4 Input terminal selection7(S3) The function depends on input terminal selection 7(f117). *2
RYn5 Input terminal selection8(S4) The function depends on input terminal selection 8(f118). *2
RYn6 Input terminal selection9(L1) The function depends on input terminal selection 9(f119). *2
RYn7 Input terminal selection10(L2) The function depends on input terminal selection 10(f120). *2
RYn8 Input terminal selection11(L3) The function depends on input terminal selection 11(f121). *2
RYn9
Intercept output to inverter
(Coast stop)
Stop the output of the inverter when turned on this signal.
(Stop the output in the secondary circuit)
RYnA Frequency priority CC-Link Signals from the CC-Link are used to start and stop operation.
RYnB Command priority CC-Link Speed commands are entered from the CC-Link.
RYnC Monitor command
When the monitor command (RYnC) is switched on, the monitored
value is set to remote register RWrn and monitoring (RXnC)
switches on. While the monitor command (RYnC) is on, the
monitored value is always update.
RYnD
Frequency setting command
(RAM)
When the frequency setting command (RYnD) is switched on, the
set frequency RWwn+1 is written to the inverter. On completion of
write, frequency setting completion (RXnD) switches on.
RYnE
Torque setting command
(RAM)
When the torque setting command (RYnE) is switched on, the set
torque RWwn+1 is written to the inverter. On completion of write,
torque setting completion (RXnE) switches on.
RYnF
Instruction code execution
request
When the instruction code execution request (RYnF) is switched
on, processing corresponding to the instruction code set to
RWwn+2 is executed. After completion of instruction code
execution, instruction code execution completion (RYnF) switches
on. When an instruction code execution error occurs, a value other
than 0 is set to the reply code (RWrn+2).
RY(n+1)0
:
RY(n+1)7
Reserved Reserved for the system. *3
RY(n+1)8 Reserved Reserved for the system. *3
RY(n+1)9 Reserved Reserved for the system. *3
RY(n+1)A Error reset request flag *2
If the error reset request flag (RY(n+1)A) is switched on only when
an inverter fault occurs, the inverter is reset and the error status flag
(RX(n+1)A) switches off. A reset request is during switched ON.
RY(n+1)B Reserved Reserved for the system. *3
RY(n+1)C
:
RY(n+1)F
Reserved Reserved for the system. *3
"n" is depend on the station number.
*1: When RYn0 and RYn1 are ON simultaneously the rotation is followed a parameter
f105(default = stop).
*2: By the input terminal function selections(f115 to f121), change of the function of the input signal is possible.
(But there are functional restrictions. Refer to the following page.)
*3: The reserved input signal should be set OFF ("0").

Other manuals for Toshiba TOSVERT VF-AS1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-AS1 and is the answer not in the manual?

Toshiba TOSVERT VF-AS1 Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-AS1
CategoryInverter
LanguageEnglish

Related product manuals