4. Functions
This option is a communication interface unit that allows the PLC program to operate,
monitor and set the parameter of the inverter as a remote station of CC-Link. It is able to
communicate with a maximum speed of 10Mbps not only transmitting bit data but also by
word data.
4.1. Initial setting
Set the following parameters of the inverter.
Name of
parameter
functions
Description
Factory
setting
CC-Link
setting
cmod
Command
mode selection
0: Terminal input enabled
1: Operation panel input enabled
(including LED/LCD option unit)
2: 2-wire RS485 communication input
3: 4-wire RS485 communication input
4: Communication option input
04
fmod
Frequency
setting mode
selection 1
1: VI/II (voltage/current input)
2: RR/S4 (potentiometer/voltage input)
3: RX (voltage input)
4: Operation panel input enabled
(including LED/LCD option input)
5: 2-wire RS485 communication input
6: 4-wire RS485 communication input
7: Communication option input
8: Optional AI1 (differential current input)
9: Optional AI2 (voltage/current input)
10: Up/Down frequency
11: Optional RP pulse input
12: Optional high-speed pulse input
13: Optional binary/BCD input
27
f420
Torque
command
selection
1: VI/II (voltage/current input)
2: RR/S4 (potentiometer/voltage input)
3: RX (voltage input)
4: Operation panel input enabled
(including LED/LCD option input)
5: 2-wire RS485 communication input
6: 4-wire RS485 communication input
7: Communications option input enabled
8: Optional AI1 (differential current input)
3 *
*Change the setting of F420 if necessary.