E6581288
− 3 
1. Overview
This option allows the VF-AS1 inverter to be connected into a CC-Link network. CC-Link
supports a maximum of 42 nodes, allowing for the Master unit and this option is based on
CC-Link Ver.1.10.
The CCL001Z is able to operate RUN/STOP, monitor the status of the inverter, set the
inverter's parameter and etc. by the CC-Link master through installing the VF-AS1. And it
can use different applications.
2. Basic specifications
<Environmental specification>
Item Specification
Operating
environment
Indoors, an altitude of 3,000m or less, where the product will
not be exposed to direct sunli
g
ht, corrosive or explosive
gases, vapor, coarse particulates including dust, and where
there is no grinding fluid or grinding oil nearby.
Ambient temperature 0 to +60
Storage temperature -25 to +65
Related temperature 20 to 93% (no condensation and absence of vapor)
Vibration 5.9 m /s
2
{0.6G} or less (10 – 55Hz)
<CC-Link communication specification>
Item Specification
Number of units
corrected
42 units max.
(
1 station occu
p
ied b
y
1 unit
)
. Ma
y
be used with
other equipment.
(*)
Baud rate 156k, 625k, 2.5M, 5M, 10Mbps
Power supply 5V DC supplied from the inverter
Station type Remote device station
Number of stations
occupied
One inverter occupies one station
Connect cable
CC-Link dedicated cable,
CC-Link Ver1.10.compatiable CC-Link dedicated cable
Maximum
transmission distance
1200m (156kbps)
*Maximum number of units connected to one master station is 42 units (when only
inverters are connected).
*If any other units are included, the number of occupied stations depends on the unit and
therefore the following conditions must be satisfied:
1. {(1×a)(2×b)(3×c)(4×d)}64
aNumber of units occupying 1 station cNumber of units occupying 3 stations
bNumber of units occupying 2 stations dNumber of units occupying 4 stations
2. {(16×A)(54×B)(88×C)}2304
ANumber of remote I/O stations 64
BNumber of remote device stations 42
CNumber of local, standby master
and intelligent device stations 26

Other manuals for Toshiba TOSVERT VF-AS1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-AS1 and is the answer not in the manual?

Toshiba TOSVERT VF-AS1 Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-AS1
CategoryInverter
LanguageEnglish

Related product manuals