1. Overview
This option allows the VF-AS1 inverter to be connected into a CC-Link network. CC-Link
supports a maximum of 42 nodes, allowing for the Master unit and this option is based on
CC-Link Ver.1.10.
The CCL001Z is able to operate RUN/STOP, monitor the status of the inverter, set the
inverter's parameter and etc. by the CC-Link master through installing the VF-AS1. And it
can use different applications.
2. Basic specifications
<Environmental specification>
Item Specification
Operating
environment
Indoors, an altitude of 3,000m or less, where the product will
not be exposed to direct sunli
ht, corrosive or explosive
gases, vapor, coarse particulates including dust, and where
there is no grinding fluid or grinding oil nearby.
Ambient temperature 0 to +60
℃
Storage temperature -25 to +65
℃
Related temperature 20 to 93% (no condensation and absence of vapor)
Vibration 5.9 m /s
2
{0.6G} or less (10 – 55Hz)
<CC-Link communication specification>
Item Specification
Number of units
corrected
42 units max.
be used with
other equipment.
(*)
Baud rate 156k, 625k, 2.5M, 5M, 10Mbps
Power supply 5V DC supplied from the inverter
Station type Remote device station
Number of stations
occupied
One inverter occupies one station
Connect cable
CC-Link dedicated cable,
CC-Link Ver1.10.compatiable CC-Link dedicated cable
Maximum
transmission distance
1200m (156kbps)
*Maximum number of units connected to one master station is 42 units (when only
inverters are connected).
*If any other units are included, the number of occupied stations depends on the unit and
therefore the following conditions must be satisfied:
1. {(1×a)+(2×b)+(3×c)+(4×d)}≦64
a:Number of units occupying 1 station c:Number of units occupying 3 stations
b:Number of units occupying 2 stations d:Number of units occupying 4 stations
2. {(16×A)+(54×B)+(88×C)}≦2304
A:Number of remote I/O stations ≦64
B:Number of remote device stations ≦42
C:Number of local, standby master
and intelligent device stations ≦26