60 CGWF-SVX01A-EN
Controls Interface
Touching the AUTO key will enable the chiller for active cooling if no diagnostic is
present. (A separate action must be taken to clear active diagnostics.)
The AUTO and STOP keys, take precedence over the Enter and Cancel keys. (While a
setting is being changed, AUTO and STOP keys are recognized even if Enter or Cancel
has not been pressed.)
The ALARMS button appears only when an alarm is present, and blinks (by alternating
between normal and reverse video) to draw attention to a diagnostic condition.
Pressing the ALARMS button takes you to the corresponding tab for additional
information.
Keypad/Display Lockout Feature
NOTE: The DynaView display and Touch Screen Lock screen is shown above. This
screen is used if the Display and touch screen and lock feature is enabled. Thirty
minutes after the last keystroke, this screen is displayed and the Display and Touch
Screen is locked out until the sequence “159 <ENTER>” is pressed.
Until the proper password is entered, there will be no access to the DynaView
screens including all reports, setpoints, and Auto/Stop/Alarms/Interlocks.
The password “159” can not be changed from either DynaView or TechView.
DISPLAY AND TOUCH SCREEN ARE LOCKED
ENTER PASSWORD TO UNLOCK
Enter
987
653
321
Cancel
0