RLC-SVX023A
20
4 UNT-PRC002-GB
Technical Data
FWD 08 12 20 30 45
Power supply (V/Ph/Hz) 230/1/50
Capacities
Cooling capacity on water (1) (kW) 5,2 8,3 15 18,8 30,1
Heating capacity on water (2) (kW) 6,3 11,9 18,9 20,9 38,2
Fan motor (type) 2 x direct drive centrifugal
Fan power input (3) (kW) 0,23 0,46 0,65 1,04 1,51
Current amps (3) (A) 1,1 2,2 3,1 4,7 5,5
Start-up amps (A) 3,2 5,5 9,3 14,1 16,5
Air flow
minimum (m
3
/h) 490 980 1400 1800 2700
nominal (m
3
/h) 820 1650 2300 3000 4500
maximum (m
3
/h) 980 1970 2600 3600 5400
Main coil
Water entering/leaving connections (type) ISO R7 rotating female
(Dia) 3/4" 3/4" 1 1/2" 1 1/2" 1 1/2"
Electric heater (accessory for blower only)
Electric power supply (V/Ph/Hz) 230/1/50 230/1/50 or 400/3/50 400/3/50 400/3/50 400/3/50
Heating capacity (kW) 2/4 8 10 12 12
Hot water coil (accessory for blower only)
Heating capacity (4) (kW) 6,3 12 17,4 22,4 34,5
G2 filter (filter box accessory)
Quantity 2 2 2 2 2
Dimensions ( LxWxth) (mm) 386x221x8 486x271x8 586x321x8 586*421*8 586*621*8
G4 filter (filter box accessory)
Quantity - 2 2 2 2
Dimensions ( LxWxth) (mm) - 486x264x48 586x314x48 586*414*48 586*614*48
Condensate pump (accessory) (type) Centrifugal
Water flow - lift height (l/h - mm) 24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5) (dB(A)) 36/40/43 38/41/44 46/50/53 47/52/57 47/52/58
Sound power level (5) (dB(A)) 46/50/53 48/51/54 56/60/63 57/62/67 57/62/68
Unit dimensions
Width x Depth (mm) 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090
Height (mm) 250 300 350 450 650
Shipped unit dimensions
Width x Depth (mm) 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333*1133
Height (mm) 260 310 360 460 660
Weight (kg) 32 46 61 76 118
Colour galvanised steel
Recommended fuse size
Unit alone (aM/gI) (A) 8/16 8/16 8/16 8/25 8/25
Unit with electric heater (gI) (A) 16 (2kW),25 (4kW) 40 (230V),3*16 (400V) 3*20 3*25 3*25
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
Condenser Water Regulating Valve
Adjustment
A separate Settings Menu tab entitled “Condenser
Head Pressure Control -Setup” that is only visible if
the configuration is selected, contain the following
settings and manual overrides for user adjustments and
commissioning all under one tab:
Off State” Output Command (0-10 Vdc, 0.1 volt
increments, Default 2.0 Vdc)
Output Voltage @Desired Minimum Flow (Adj: 0 to 10.0
in 0.1 volt increments, Default 2.0 Vdc)
Desired Minimum Flow (Adj:0-100% of full flow in
1%intervals, Default 20%)
Output Voltage @Desired Maximum Flow (Adj: 0 to 10.0
in 0.1 volt increments (or finer),Default 10 Vdc)
Actuator Stroke Time (Min to Max Range Time)(Adj: 1 to
1000 seconds, in 1 second increments, Default 30s)
Damping Coefficient (adj: 0.1 to 1.8, in 0.1 increments,
Default .5)
Head Pressure Control Override (enumeration of:
disabled (auto),off” state, minimum, maximum
(100%),) default : disabled (auto). When this setting is in
“disabled (auto)”
Condenser Water Pump Prerun Time
WARNING: In low temperature chilled water
applications, in the case of a power loss, there is a risk
of a condenser freeze-up. For low temperature chilled
water applications, it is recommended to take freeze
protection measures.
Installation - Mechanical

Other manuals for Trane CITY RTSF Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane CITY RTSF Series and is the answer not in the manual?

Trane CITY RTSF Series Specifications

General IconGeneral
BrandTrane
ModelCITY RTSF Series
CategoryChiller
LanguageEnglish

Related product manuals