RLC-SVX023A
22
4 UNT-PRC002-GB
Technical Data
FWD 08 12 20 30 45
Power supply (V/Ph/Hz) 230/1/50
Capacities
Cooling capacity on water (1) (kW) 5,2 8,3 15 18,8 30,1
Heating capacity on water (2) (kW) 6,3 11,9 18,9 20,9 38,2
Fan motor (type) 2 x direct drive centrifugal
Fan power input (3) (kW) 0,23 0,46 0,65 1,04 1,51
Current amps (3) (A) 1,1 2,2 3,1 4,7 5,5
Start-up amps (A) 3,2 5,5 9,3 14,1 16,5
Air flow
minimum (m
3
/h) 490 980 1400 1800 2700
nominal (m
3
/h) 820 1650 2300 3000 4500
maximum (m
3
/h) 980 1970 2600 3600 5400
Main coil
Water entering/leaving connections (type) ISO R7 rotating female
(Dia) 3/4" 3/4" 1 1/2" 1 1/2" 1 1/2"
Electric heater (accessory for blower only)
Electric power supply (V/Ph/Hz) 230/1/50 230/1/50 or 400/3/50 400/3/50 400/3/50 400/3/50
Heating capacity (kW) 2/4 8 10 12 12
Hot water coil (accessory for blower only)
Heating capacity (4) (kW) 6,3 12 17,4 22,4 34,5
G2 filter (filter box accessory)
Quantity 2 2 2 2 2
Dimensions ( LxWxth) (mm) 386x221x8 486x271x8 586x321x8 586*421*8 586*621*8
G4 filter (filter box accessory)
Quantity - 2 2 2 2
Dimensions ( LxWxth) (mm) - 486x264x48 586x314x48 586*414*48 586*614*48
Condensate pump (accessory) (type) Centrifugal
Water flow - lift height (l/h - mm) 24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5) (dB(A)) 36/40/43 38/41/44 46/50/53 47/52/57 47/52/58
Sound power level (5) (dB(A)) 46/50/53 48/51/54 56/60/63 57/62/67 57/62/68
Unit dimensions
Width x Depth (mm) 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090
Height (mm) 250 300 350 450 650
Shipped unit dimensions
Width x Depth (mm) 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333*1133
Height (mm) 260 310 360 460 660
Weight (kg) 32 46 61 76 118
Colour galvanised steel
Recommended fuse size
Unit alone (aM/gI) (A) 8/16 8/16 8/16 8/25 8/25
Unit with electric heater (gI) (A) 16 (2kW),25 (4kW) 40 (230V),3*16 (400V) 3*20 3*25 3*25
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
Power Supply Wiring
Model RTSF chillers are designed according to European
standard EN 60204-1; therefore, all power supply wiring
must be sized and selected accordingly by the project
engineer.
Water Pump Power Supply
Provide power supply wiring with fused disconnect for
both the chilled water and condenser water pumps.
Electrical Panel Power Supply
Power supply wiring instructions for the starter/control
panel are:
Run the line voltage wiring in conduit to the access
opening(s) on the starter/control panel. See the product
catalog for wire sizing and selection information
and refer to general data that show typical electrical
connection sizes and locations. Always refer to submittal
information for your actual unit specifications.
Some connections required the user to provide an
external source of power. The 110V control power
transformer is not sized for additional load.
CAUTION
Unit with AFD version must not be linked to the neutral
wiring of the installation.
Units are compatible with the following neutral
operating conditions:
TNS IT TNC TT
Standard Special Special Special
- on request - on request - on request
Differential protection should be suited for industrial
machinery with current leak which can be higher than
500 mA (several motors and frequency drives).
CAUTION! To avoid corrosion, overheating or general
damage, at terminal connections, unit is designed for
copper Conductors only. In case of aluminum cable,
bi-material connecting devices are mandatory. Cable
routing inside control panel should be made case by
case by installer.
Compressor Motor Phase
Sequencing
Always verify that proper rotation of the chiller
compressor is established before the machine is started.
Proper motor rotation requires confirmation of the
electrical phase sequence of the power supply. The
motor is internally connected for clockwise rotation with
the incoming power supply phased A, B, C (L1, L2, L3).
To confirm the correct phase sequence (ABC), use a
phase meter.
Basically, voltages generated in each phase of a
polyphase alternator or circuit are called phase voltages.
In a 3-phase circuit, 3 sine wave voltages are generated,
differing in phase by 120 electrical degrees. The order
in which the 3 voltages of a 3-phase system succeed
one another is called phase sequence or phase rotation.
This is determined by the direction of rotation of the
alternator. When rotation is clockwise, phase sequence is
usually called “ABC.
This direction may be reversed outside the alternator
by interchanging any two of the line wires. It is this
possible interchange of wiring that makes a phase
sequence indicator necessary if the operator is to quickly
determine the phase rotation of the motor.
Module and Control Panel
Connectors
All connectors can be unplugged or the wires can be
removed. If an entire plug is removed, make sure the
plug and the associated jack are marked for proper
location identification during reinstallation.
All electrical drawings, schematics and control panel
layout are included in the documentation package sent
with the chiller.
Installation - Electrical

Other manuals for Trane CITY RTSF Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane CITY RTSF Series and is the answer not in the manual?

Trane CITY RTSF Series Specifications

General IconGeneral
BrandTrane
ModelCITY RTSF Series
CategoryChiller
LanguageEnglish

Related product manuals