RLC-SVX023A
4
4 UNT-PRC002-GB
Technical Data
FWD 08 12 20 30 45
Power supply (V/Ph/Hz) 230/1/50
Capacities
Cooling capacity on water (1) (kW) 5,2 8,3 15 18,8 30,1
Heating capacity on water (2) (kW) 6,3 11,9 18,9 20,9 38,2
Fan motor (type) 2 x direct drive centrifugal
Fan power input (3) (kW) 0,23 0,46 0,65 1,04 1,51
Current amps (3) (A) 1,1 2,2 3,1 4,7 5,5
Start-up amps (A) 3,2 5,5 9,3 14,1 16,5
Air flow
minimum (m
3
/h) 490 980 1400 1800 2700
nominal (m
3
/h) 820 1650 2300 3000 4500
maximum (m
3
/h) 980 1970 2600 3600 5400
Main coil
Water entering/leaving connections (type) ISO R7 rotating female
(Dia) 3/4" 3/4" 1 1/2" 1 1/2" 1 1/2"
Electric heater (accessory for blower only)
Electric power supply (V/Ph/Hz) 230/1/50 230/1/50 or 400/3/50 400/3/50 400/3/50 400/3/50
Heating capacity (kW) 2/4 8 10 12 12
Hot water coil (accessory for blower only)
Heating capacity (4) (kW) 6,3 12 17,4 22,4 34,5
G2 filter (filter box accessory)
Quantity 2 2 2 2 2
Dimensions ( LxWxth) (mm) 386x221x8 486x271x8 586x321x8 586*421*8 586*621*8
G4 filter (filter box accessory)
Quantity - 2 2 2 2
Dimensions ( LxWxth) (mm) - 486x264x48 586x314x48 586*414*48 586*614*48
Condensate pump (accessory) (type) Centrifugal
Water flow - lift height (l/h - mm) 24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5) (dB(A)) 36/40/43 38/41/44 46/50/53 47/52/57 47/52/58
Sound power level (5) (dB(A)) 46/50/53 48/51/54 56/60/63 57/62/67 57/62/68
Unit dimensions
Width x Depth (mm) 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090
Height (mm) 250 300 350 450 650
Shipped unit dimensions
Width x Depth (mm) 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333*1133
Height (mm) 260 310 360 460 660
Weight (kg) 32 46 61 76 118
Colour galvanised steel
Recommended fuse size
Unit alone (aM/gI) (A) 8/16 8/16 8/16 8/25 8/25
Unit with electric heater (gI) (A) 16 (2kW),25 (4kW) 40 (230V),3*16 (400V) 3*20 3*25 3*25
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
Introduction
Unit Description
The RTSF units are helical-rotary type, water-cooled,
liquid chillers, designed for installation indoors.
The RTSF units are packaged with an evaporator
and condenser.
Note: Each RTSF unit is a completely assembled,
hermetic package that is factory-piped, wired, leak
tested, dehydrated, charged and tested for proper control
operations prior to shipment. The chilled water inlet and
outlet openings are covered for shipment.
The RTSF series features Trane’s exclusive Adaptive
Control logic with UC800 controls. It monitors the control
variables that govern the operation of the chiller unit.
Adaptive Control logic can correct these variables, when
necessary, to optimize operational efficiencies, avoid
chiller shutdown, and keep producing chilled water.
Compressor loading/unloading is provided by AFD
(Adaptive Frequency Drive) coordinated with slide
valve operation.
Each refrigerant circuit is provided with filter, sight glass,
electronic expansion valve, and charging valves on
the RTSF.
The evaporator and condenser are manufactured
in accordance with Pressure Equipment Directive
standards. The evaporator and the condenser are
insulated according the option ordered. Both evaporator
and condenser water pipes are equipped with water
drain and vent connections.
Refrigerant
Consult the addendum to Manuals for units with
refrigerant, for conformity to the Pressure Equipment
Directive (PED) 97/23/EC or 2014/68/EU and Machinery
Directive 2006/42/EC and for specific caution for R1234ze.
Maintenance contract
It is strongly recommended that you sign a maintenance
contract with your local Trane Service Agency. This
contract provides regular maintenance of your
installation by a specialist in our equipment. Regular
maintenance ensures that any malfunction is detected
and corrected in good time and minimizes the possibility
that serious damage will occur. Finally, regular
maintenance ensures the maximum operating life of
your equipment. We would remind you that failure to
respect these installation and maintenance instructions
may result in immediate cancellation of the warranty.
Training
To assist you in obtaining the best use of it and
maintaining it in perfect operating condition over a long
period of time, the manufacturer has at your disposal
a refrigeration and air conditioning service school. The
principal aim of this is to give operators and technicians
a better knowledge of the equipment they are using,
or that is under their charge. Emphasis is particularly
given to the importance of periodic checks on the
unit operating parameters as well as on preventive
maintenance, which reduces the cost of owning the unit
by avoiding serious and costly breakdown.

Other manuals for Trane CITY RTSF Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane CITY RTSF Series and is the answer not in the manual?

Trane CITY RTSF Series Specifications

General IconGeneral
BrandTrane
ModelCITY RTSF Series
CategoryChiller
LanguageEnglish

Related product manuals