HHaazzaarrddoouuss CChheemmiiccaallss!!
FFaaiilluurree ttoo ffoollllooww tthhiiss ssaaffeettyy pprreeccaauuttiioonn ccoouulldd
rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy.. CCooiill cclleeaanniinngg
aaggeennttss ccaann bbee eeiitthheerr aacciiddiicc oorr hhiigghhllyy aallkkaalliinnee aanndd
ccaann bbuurrnn sseevveerreellyy iiff ccoonnttaacctt wwiitthh sskkiinn oorr eeyyeess
ooccccuurrss..
HHaannddllee cchheemmiiccaall ccaarreeffuullllyy aanndd aavvooiidd ccoonnttaacctt wwiitthh
sskkiinn.. AALLWWAAYYSS wweeaarr PPeerrssoonnaall PPrrootteeccttiivvee
EEqquuiippmmeenntt ((PPPPEE)) iinncclluuddiinngg ggoogggglleess oorr ffaaccee sshhiieelldd,,
cchheemmiiccaall rreessiissttaanntt gglloovveess,, bboooottss,, aapprroonn oorr ssuuiitt aass
rreeqquuiirreedd.. FFoorr ppeerrssoonnaall ssaaffeettyy rreeffeerr ttoo tthhee cclleeaanniinngg
aaggeenntt mmaannuuffaaccttuurreerrss MMaatteerriiaallss SSaaffeettyy DDaattaa SShheeeett
aanndd ffoollllooww aallll rreeccoommmmeennddeedd ssaaffee hhaannddlliinngg
pprraaccttiicceess..
It should be noted that the water quality should be
checked periodically (See below).
Table 59. Water quality
Scaling
Amount
Calcium and magnesium (total
hardness) Less than 350 ppm
Corrosion
pH
7-9.5
Hydrogen Sulfide Less than 1 ppm
Table 59. Water quality (continued)
Scaling
Amount
Sulfates
Less than 25 ppm
Chlorides
Less than 125 ppm
Carbon Dioxide
Less than 75 ppm
Total dissolved solids (TDS) Less than 1000 ppm
Biological Growth
Iron Bacteria Low
Erosion
Suspended Solids
Low
Condensate Trap
For units incorporating a negative trap design, ensure
that the condensate system is primed with water at all
times. Allowing a negative, pressure condensate
system to run dry could cause a break in the
condensate seal allowing the fan to draw water from
the condensate line to spray moisture into the
mechanical system. By maintaining a primed
condensate trap, a seal will be created and will help
prevent these complications.