Maintenance
176 RT-SVX36K-EN
Load and Motor
1-03 Torque Characteristics Variable Torque Variable Torque
1-20 (TR150)
1-21 (TR200)
Motor Power [HP] Per Motor Nameplate HP
Sum of HP Per Motor
Nameplate HP [dual motors
on 60-75T]
hp
1-22 Motor Voltage
Per Motor Nameplate
Voltage
Per Motor Nameplate
Voltage
V
1-23 Motor Frequency Per Motor Nameplate Per Motor Nameplate Hz
1-24 Motor Current Per Motor Nameplate FLA
Sum of FLA Per Motor
Nameplate FLA [dual motors
on 60-75T]
A
1-25 Motor Nominal Speed
Per Motor Nameplate Rated
Speed
Per Motor Nameplate Rated
Speed
RPM
1-39 Motor Poles 4
6 if Motor Nameplate Rated
Speed ~1200 RPM
4 if Motor Nameplate Rated
Speed > 1200 RPM
1-73 Flying Start Enabled Enabled
1-90 Motor Thermal Protection ETR Trip1 ETR Trip1
Brakes
2-00 DC Hold/Preheat Current 0 0 %
2-01 DC Brake Current 0 0 %
2-04
DC Brake Cut In Speed
[Hz]
10 10 Hz
Reference / Ramps
3-03 Maximum Reference 60
83 (4-pole motor), 120
(6-pole motor)
Hz
3-16 Reference 2 Source No function No function
3-17 Reference 3 Source No function No function
3-41 Ramp 1 Ramp up Time 30 30 s
3-42 Ramp 1 Ramp Down Time 30 30 s
Limits / Warnings
4-12
Motor Speed Low Limit
[Hz]
22 15 Hz
4-14
Motor Speed High Limit
[Hz]
60
If ID139 = 4 poles then
81.8 - 20, 24, 25, 29T Units
75.6 - 60, 73T Units
67.8 - 30, 36, 40, 48, 70, 75,
80, 89T Units
61.7 - 50, 55, 59T Units
If ID139 = 6 poles then
120 - 20, 24, 25, 29T Units
113.4 - 60, 73T Units
101.7 - 30, 36, 40, 48, 70,
75, 80, 89T Units
92.5 - 50, 55, 59T Units
Hz
4-18 Current Limit 100 100 %
4-19 Max Output Frequency 60 120 Hz
Digital In/Out
5-12 Terminal 27 Digital Input Coast inverse Coast inverse
5-13 Terminal 29 Digital Input No operation No operation
5-40 Function Relay
Relay 1 active No alarm,
Relay 2 active Motor
Running
(Relay 1 [160], Relay 2 [5])
Relay 1 active No alarm,
Relay 2 active Motor
Running
(Relay 1 [160], Relay 2 [5])
Analog In/Out
6-14
Terminal 53 Low Ref./
Feedb. Value
22 15
6-15
Terminal 53 High Ref./
Feedb. Value
60
83 (4-pole motor), 120
(6-pole motor)
Table 78. Supply and exhaust/return fan VFD programming parameters (continued)
Menu ID Name FC DDP Unit

Table of Contents

Other manuals for Trane IntelliPak

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane IntelliPak and is the answer not in the manual?

Trane IntelliPak Specifications

General IconGeneral
BrandTrane
ModelIntelliPak
CategoryAir Conditioner
LanguageEnglish

Related product manuals