Maintenance
RT-SVX36K-EN 177
eFlex™ Compressor VFD Programming
Parameters
The VFD is factory programmed and should not be
modified in the field. It is specifically matched to the
compressor. Should replacing a VFD become necessary,
the replacement is configured with all ofTrane's operating
parameters. Do not use any other type or brand of VFD
when replacing the VFD.
Supply and Exhaust Fan VFD Programming
Parameters
Units shipped with an optional variable frequency drive
(VFD) are preset and run tested at the factory. If a problem
with a VFD occurs, ensure that the programmed
parameters listed in Table 78 have been set before
replacing the drive.
Note: Check to make sure that parameter 1-23 is set to 60
Hz (or 50 Hz where applicable) and that parameter
0-06 is set to the correct supply voltage/frequency
range.To check parameter 1-23 press the [Main
Menu] button (twice ifTR150 drive) (press [Back]
button if the main menu does not display), use the
[
] button to scroll down to Load & Motor, press
OK, use the [
] button to select 1-2, press OK, and
finally use the [
] button until parameter 1-23 is
displayed. Parameter 1-23 can then be modified by
pressing OK button and using [
] and [] buttons.
When the desired selection has been made, press
the OK button.
Should replacing a VFD become necessary, the
replacement is not configured with all ofTrane's operating
parameters.The VFD must be programmed before
attempting to operate the unit.To verify and/or program a
VFD, use the following steps:
1. At the unit, turn the 115 volt control circuit switch 1S70
to the Off” position.
2. Turn the 24 volt control circuit switch to the Off'
position.
HIGH VOLTAGE IS PRESENT ATTERMINAL BLOCK 1TB1
OR UNIT DISCONNECT SWITCH 1S14.
3. To modify parameters:
a. Press Main Menu button (twice ifTR150 drive)
(press [Back] button if the main menu does not
display)
b. Use the [
] and [] buttons to find the parameter
menu group (first part of parameter number)
c. Press [OK]
Special Function
14-01 Switching Frequency
8.0 kHz (drive dependant,
set to 5kHz if 8kHz not
available)
8.0 kHz (drive dependant,
set to 5kHz if 8kHz not
available)
14-11 (TR200 only)
Mains Voltage at Mains
Fault
400V for 460V 60Hz unit,
leave at default otherwise
400V for 460V 60Hz unit,
leave at default otherwise
14-12
Function at Mains
Imbalance
Derate Derate
14-20 Reset Mode Automatic reset x 5 Automatic reset x 5
14-50 RFI Filter Off Off
14-60 (TR200 only)
Function at Over
Temperature
Derate Derate
14-61 (TR200 only)
Function at Inverter
Overload
Derate Derate
Note: For 50Hz units parameters 0-06 Grid Type (TR150s only) and 1-23 Motor Freq will need to be set accordingly.
Table 78. Supply and exhaust/return fan VFD programming parameters (continued)
Menu ID Name FC DDP Unit
WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. For variable frequency drives
or other energy storing components provided byTrane
or others, refer to the appropriate manufacturer’s
literature for allowable waiting periods for discharge of
capacitors. Verify with an appropriate voltmeter that all
capacitors have discharged. Failure to disconnect power
and discharge capacitors before servicing could result
in death or serious injury.
For additional information regarding the safe discharge
of capacitors, see PROD-SVB06A-EN.
WARNING
Live Electrical Components!
During installation, testing, servicing and
troubleshooting of this product, it may be necessary to
work with live electrical components. Have a qualified
licensed electrician or other individual who has been
properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical
components could result in death or serious injury.

Table of Contents

Other manuals for Trane IntelliPak

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane IntelliPak and is the answer not in the manual?

Trane IntelliPak Specifications

General IconGeneral
BrandTrane
ModelIntelliPak
CategoryAir Conditioner
LanguageEnglish

Related product manuals