Error Codes and Exceptions
Exceptions
There are exceptions to be noted when using the thermostat.These exceptions are:
If the indoor or outdoor temperature is lower or higher than the measuring range, the
temperature display will blink either “--F” (Fahrenheit) or “--C” (Celsius) at 1.5 seconds ON and
0.5 seconds OFF. All other outputs remain functional. Display range is -45°F to 199°F (-42.8°C
to 92.8°C))
If the system fails to access EEPROM for 10 minutes, the system will blink with E3 (3s= Error
Code and 1s= Time Display). However, it will continue to operate at its current mode (refer to
the section,
“Error Codes,” p. 48).
If any of the above exceptions listed should occur, the temperature control will continue to
operate normally and all outputs remain functional.
The humidity sensor error blinks 1.5 seconds ON and 0.5 seconds OFF in the humidity reading
area and blink Error Code E1 (3s= Error Code and 1s= Time Display). The humidity function will
continue to operate for readings 0% to 100% for both internal/external humidity sensors.
However, the humidity function will shut down for a communication error with the internal
humidity sensor and with less that 4 mA for external humidity sensor.

Table of Contents

Other manuals for Trane THT02775

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane THT02775 and is the answer not in the manual?

Trane THT02775 Specifications

General IconGeneral
BrandTrane
ModelTHT02775
CategoryThermostat
LanguageEnglish

Related product manuals