Doc: 70-00-0792B V1.3, 20220830 © Vector Controls GmbH, Switzerland Page 4-34
Subject to change without notice www.vectorcontrols.com
2 Technical Specifications
Screw terminals
Wire 0.15…2.05 mm2 (AWG 26…14)
Temperature range
Accuracy 0…50°C
0…50°C (32…122°F)
0.5°C (1°F)
Digital and temperature input
Temperature range
Temperature accuracy
Selectable via parameter
-20…60°C (-4…140°F)
0.5°C (1°F) at 0…50°C (32…122°F)
1.0°C (2°F) at <0°C (<32°F), >50°C (>122°F)
Type & range of temperature sensor
NTC (Sxx-Tn10): -40…140°C (-40…284°F)
0…250 VAC, resistive load current 5A, inductive 2A
Insulation strength
between relays and system electronics
between neighboring contacts
2500V to EN 60 730-1
2500V to EN 60 730-1
2.B (micro-disconnection)
Network
(TRA-F121-A only)
Hardware interface
Max nodes per network
Max nodes per segment
RS485 in accordance with EIA/TIA 485
247
128
Shielded Twisted Pair (STP) cable
100 – 130 Ω
The communication circuitry is isolated
According Modbus manual (Modbus over serial
line)
Recommended maximum length per chain
Modbus RTU (www.modbus.org)
38400 baud rate, even parity, 1 stop bit
Communication speed (baud rate)
2400, 4800, 9600, 19200, 38400, 57600, 115200
Modbus RTU protocol (8 data bits)
no parity – 1 or 2 stop bits;
even or odd parity – 1 stop bit
Operation
Climatic conditions
Temperature
Humidity
To IEC 721-3-3
class 3K5
0…50 °C (32…122 °F)
<85 % RH non-condensing
Transport & storage
Climatic conditions
Temperature
Humidity
Mechanical conditions
To IEC 721-3-2 and IEC 721-3-1
class 3K3 and class 1K3
0…50 °C (32…122 °F)
<95 % RH non-condensing
class 2M2
Fire proof PC+ABS plastic (UL94 class V-0)
Dimensions front part (H x W x D)
Dimensions back part (H x W x D)
88 x 88 x 16 mm (3.5 x 3.5 x 0.6 in)
67 x 61 x 25 mm (2.6 x 2.4 x 1.0 in)
Weight (including package)
2.1 Product testing and certification
Declaration of
Conformity
Information on the conformity of our products can be found on our website
www.vectorcontrols.com on the corresponding product page under "Downloads".