Appendix en
Installation and operating instructions Wilo-Control EC-L 101
Data type Description
BOOL
Boolean value is a parameter with exactly two states (0 — false and 1 —
true). Generally, all values greater than zero are classified as true.
BITMAP*
Is an array of 16Boolean values (bits). Values are indexed from 0 to 15.
The number read from or written to the register is the sum of all bits with
value 1 multiplied by 2 to the power of its index.
▪Bit 0: 2
0
=1
▪Bit 1: 2
1
=2
▪Bit 2: 2
2
=4
▪Bit 3: 2
3
=8
▪Bit 4: 2
4
=16
▪Bit 5: 2
5
=32
▪Bit 6: 2
6
=64
▪Bit 7: 2
7
=128
▪Bit 8: 2
8
=256
▪Bit 9: 2
9
=512
▪Bit 10: 2
10
=1024
▪Bit 11: 2
11
=2048
▪Bit 12: 2
12
=4096
▪Bit 13: 2
13
=8192
▪Bit 14: 2
14
=16384
▪Bit 15: 2
15
=32768 every 0
BITMAP32
Is an array of 32Boolean values (bits). The calculation details can be
found in the description for Bitmap.
* Example for clarification:
Bit 3, 6, 8, 15 are 1 all others are 0. The sum is then 2
3
+2
6
+2
8
+2
15
= 8+64+256+32768
= 33096. The other way round is also possible. Based on the bit with the highest index,
check whether the read number is greater than/equal to the power of two. If this is the
case, bit 1 is set and the power of two is deducted from the number. Then the check
with the bit with the next lower index and the recently calculated residual number is re-
peated until bit 0 is obtained for bit or the residual number is zero. Example for clarific-
ation: The read number is 1416. Bit 15 will be 0, since 1416<32768. Bit 14 to 11 will
also be 0. Bit 10 will be 1, since 1416>1024. The remainder will be 1416-1024=392.
Bit 9 will be 0, since 392<512. Bit 8 will be 1 since 392>256. The remainder will be
392-256=136. Bit 7 will be 1 since 136>128. The remainder will be 136-128=8. Bit 6
to 4 will be 0. Bit 3 will be 1 since 8=8. The remainder will be 0. Residual bits will thus be
2 to 0.
13.6 ModBus: Parameter overview
Holding register
(Protocol)
Name Data type Scale & unit Elements Access Added
40001
(0)
Version communica-
tion profile
UINT16 0.001 R 31.000
40002
(1)
Wink service BOOL RW 31.000
40003
(2)
Switch box type ENUM 0. SC
1. SC...FC
2. SCe
3. CC
4. CC...FC
5. CCe
6. SCe NWB
7. CCe NWB
8. EC
9. ECe
10. ECe NWB
R 31.000
40014
(13)
Bus command timer ENUM 0. -
1. Off
2. Set
3. Active
4. Reset
5. Manual
RW 31.000