EasyManuals Logo
Home>Xantrex>Portable Generator>Automatic Generator

Xantrex Automatic Generator User Manual

Xantrex Automatic Generator
124 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #76 background imageLoading...
Page #76 background image
Configuration
3–28 975-0082-01-01
Generator Configuration menu
The Generator Configuration (AGS Gen Config) menu contains additional
options for configuring the Auto Gen Start for your make and model of
generator. The items on this menu include the settings you automatically
select when you select a Gen Type (see “Gen Type” on page 3–16). This
menu also allows you to set the generator exercise period.
The Generator Configuration menu contains the following items:
“Starter Cool Down”
“Max Run Time”
“Exercise Per”
“Exercise Dur”
“Exercise Time”
•“Relay3
•“Run Hold Time
•“Crank Time
•“Crank Retry Time
“Preheat Time”
“Start Tries”
Starter Cool Down
Purpose The Starter Cool Down setting allows you to set an interval between start
attempts if the generator fails to start on the first attempt. This time period
allows the start motor to cool sufficiently before the Auto Gen Start
signals it to begin cranking again.
When to use This setting is automatically configured when you select a “Gen Type” for
your generator. You should manually set “Starter Cool Down” if you need
to customize your “Gen Type” on the advice of your generator
manufacturer or authorized service personnel.
Values Default
1s to 250s (increments of 1s) 60s

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Xantrex Automatic Generator and is the answer not in the manual?

Xantrex Automatic Generator Specifications

General IconGeneral
BrandXantrex
ModelAutomatic Generator
CategoryPortable Generator
LanguageEnglish