EasyManuals Logo
Home>Xinje>Industrial Equipment>MP Series

Xinje MP Series User Manual

Xinje MP Series
74 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #32 background imageLoading...
Page #32 background image
28
3. Connection diagram of MP and other
devices
3-1Xinje FC/XC series PLC
1. Software settings
Parameters
Recommended Settings
Download Port
9-Pin communication port
PLC Port
Communication port
Communication Type
RS232
Communication Distance
15m
Data Bit
8
Stop Bit
1
Verification Mode
Odd
Baud Rate
9600
Modbus Number
1
2. Operational Address
(1) FC Series
FC Address
Operational Range
Data Type
Description
X
0~337
Bit
External input coil
Y
0~337
Bit
External output coil
M
0~383
Bit
Internal coil
SM
0~96
Bit
Internal special register
T
0~128
Bit
Timer
C
0~128
Bit
Counter
W
0~2047
Word/DWord
Data register
FW
0~191
Word/DWord
FlashROM register
TW
0~127
Word/
Value of Timer
CW
0~127
Word/
Value of Counter
SW
0~111
Word//DWord
Special register
WX
0~13
Word//DWord
Input coil as a register
WY
0~13
Word//DWord
Output relay as a register
WM
0~23
Word//DWord
Internal relay as a
register