66
3-17Bosch Rexroth IndraControl L40 series
1. Software settings
parameters
Recommended settings
MP communication port
Communication port
PLC communication port
Terminal port
Communication type
RS232
Communication distance
15m
Data bit
8
Stop bit
1
Verification mode
None
Baud rate
38400
Modbus number
1
2. Address
PLC address
Operational range
Data type
Description
X
0~9999
Bit
External input and output coil
B
0~9999
Byte
Registers
W
0~9999
Word
Registers
D
0~9999
D Word
Registers
R
0~9999
D Word
Registers
SB
0~9999
Byte
Registers
SW
0~9999
Word
Registers
SD
0~9999
D Word
Registers
3. Connection type
Suitable model MP360-LMP760-T