39
3-5KOYO S series
1. Software settings
parameters
Recommended settings
MP communication port
Communication port
PLC communication port
Terminal port or expanded communication port
Communication type
RS232
Communication distance
15m
Data bit
8
Stop bit
1
Verification mode
Odd
Baud rate
9600
Modbus number
MP360-L/MP760-T1
2. Address
PLC address
Operational range
Data type
Description
M
0~777
Bit
Internal auxiliary coil
I
0~777
Bit
External input coil
Q
0~777
Bit
External output coil
SP
0~777
Bit
Internal auxiliary coil
T
0~777
Bit
Timer coil
C
0~777
Bit
Counter coil
S
0~777
Bit
Stepping coil
R
0~41200
Word/D Word
Data registers
3. Connection Type
(1) connect to CPU or communication unit 25 pin (RS232 communication serial port)
Suitable modelMP330MP330-SMP360-LMP760-T