EasyManuals Logo

York ZF 240 Series User Manual

York ZF 240 Series
55 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #17 background imageLoading...
Page #17 background image
1061903-XIM-A-0713
Johnson Controls Unitary Products 17
Table 9: Electrical Data
ZF180-240 - High Static Drive
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Electric Heat Option
MCA
1
(Amps)
1. Minimum Circuit Ampacity.
Max Fuse
2
/
Breaker
3
Size
(Amps)
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
RLA LRA MCC
FLA FLA Model kW Stages Amps
C1 C2 C1 C2 C1 C2
180
(15)
380-3-50 18.6 14.5 100.0 90.5 26.0 20.3 2.1 6.3
None -- -- -- 49 60
E18 11.3 1 17.1 49 60
E36 22.6 2 34.3 51 60
E54 33.8 2 51.4 73 80
E72 45.1 2 68.6 90 100
415-3-50 18.6 14.5 111.0 101.0 26.0 20.3 2.1 6.7
None -- -- -- 49 60
E18 13.5 1 18.7 49 60
E36 26.9 2 37.4 56 60
E54 40.0 2 56.2 79 80
E72 53.8 2 74.9 84 90
240
(20)
380-3-50 20.7 20.0 110.0 110.0 29.0 28.0 2.1 8.2
None -- -- -- 60 70
E18 11.3 1 17.1 60 70
E36 22.6 2 34.3 60 70
E54 33.8 2 51.4 75 80
E72 45.1 2 68.6 96 100
415-3-50 20.7 20.0 118.0 118.0 29.0 28.0 2.1 9.1
None -- -- -- 60 70
E18 13.5 1 18.7 60 70
E36 26.9 2 37.4 60 70
E54 40.0 2 56.2 82 80
E72 53.8 2 74.9 87 90