ACH580 E-Clipse bypass and packaged drive user manual 237
Technical data
Technical data
Power connection terminals
The following tables show maximum wire size and required tightening torque for
incoming power, grounding and motor terminals.
208/230 Volt
Output
Ratings
Base
Drive
Frame
Size
Maximum Power Wiring Data
Type Code
1
AHP
Circuit
Breaker
UL
(NEMA)
Type 1
and 12
Circuit
Breaker
UL (NEMA)
Type 3R
Disconnect
Switch
UL (NEMA)
Type 1
and 12
Disconnect
Switch
UL (NEMA)
Type 3R
Motor
Terminals
Ground
Lugs
UL
(NEMA)
Type 1
and 12
Ground
Lugs
UL
(NEMA)
Type 3R
ACH580-PxR-04A6-2 4.6 1 R1
#10
62 in-lbs
#10
62 in-lbs
#10
55 in-lbs
#10
55 in-lbs
#10
0.7 ft-lbs
#2
50 in-lbs
#2
50 in-lbs
ACH580-PxR-06A6-2 6.6 1.5 R1
ACH580-PxR-07A5-2 7.5 2 R1
ACH580-PxR-10A6-2 10.6 3 R1
ACH580-PxR-017A-2 16.7 5 R1
#6
62 in-lbs
#6
62 in-lbs
#6
55 in-lbs
#6
55 in-lbs
ACH580-PxR-024A-2 24.2 7.5 R2
#6
1.1 ft-lbs
ACH580-PxR-031A-2 30.8 10 R2
#4
62 in-lbs
#4
62 in-lbs
#4
55 in-lbs
#4
55 in-lbs
ACH580-PxR-046A-2 46.2 15 R3
#2
62 in-lbs
#2
62 in-lbs
#2
55 in-lbs
#2
55 in-lbs
#2
2.6 ft-lbs
ACH580-PxR-059A-2 59.4 20 R3
#1
62 in-lbs
#1
62 in-lbs
#1
55 in-lbs
#1
55 in-lbs
ACH580-PxR-075A-2 74.8 25 R4
#1/0
62 in-lbs
#1/0
62 in-lbs
#1/0
55 in-lbs
#1/0
55 in-lbs
#1
3.0 ft-lbs
ACH580-PxR-088A-2 88 30 R5
#2/0
124 in-lbs
Consult
Factory
#2/0
275 in-lbs
Consult
Factory
#2/0
4.1 ft-lbs
#1/0
50 in-lbs
Consult
Factory
ACH580-PxR-114A-2 114 40 R5
#1/0
124 in-lbs
#4/0
275 in-lbs
ACH580-PxR-143A-2 143 50 R6
#3/0
124 in-lbs
200 MCM
275 in-lbs
300 MCM
22.1 ft-lbs
ACH580-PxR-169A-2 169 60 R7
#4/0
124 in-lbs
500 MCM
29.5 ft-lbs
ACH580-PxR-211A-2 211 75 R7
2 X 500
MCM
274 in-lbs
2 X 500
MCM
274 in-lbs
ACH580-PxR-248A-2 248 100
2
R8
373
MCM
274 in-lbs
2 x 300
MCM
29.6 ft-lbs
1) “PxR” represents both PCR and PDR.
2) 100 HP @ 230V.