EasyManuals Logo
Home>ABB>Controller>ACS 604

ABB ACS 604 User Manual

ABB ACS 604
82 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #42 background imageLoading...
Page #42 background image
Appendix A – ACS/ACC/ACP 604/607 Technical Data
A-4 ACx=ACS/ACC/ACP ACS/ACC/ACP 604/607 Drives
Input Power
Connection
Voltage (
U
1
):
380/400/415 VAC 3-
phase
± 10% for 400 VAC units
380/400/415/440/460/480/500 VAC 3-
phase
± 10% for 500 VAC units
525/550/575/600/660/690 VAC 3-
phase
± 10% for 690 VAC units
(690 VAC 3-
phase
-10
...
+ 5% for ACx 607 units)
Short Circuit Capability: The rated short time withstand current of
ACx 600 is 50 kA 1 s.
Measured according to US standards ACS 604 / ACS 607 (100...400 kVA):
Suitable for use in a circuit capable of delivering not more than 65 kA rms
symmetrical amperes at 480 V maximum (500 V units), and at 600 V
maximum (690 V units).
Frequency: 48 to 63 Hz, maximum rate of change 17%/s
Imbalance: Max.
± 3% of nominal phase to phase input voltage
Fundamental Power Factor (cos
j
1
): 0.97 (at nominal load)
Motor Connection
Voltage (
U
2
): 0 to
U
1
,
3-phase symmetrical
Frequency: DTC mode: 0 to 3.2 ·
f
FWP
. Maximum frequency 300 Hz.
f
FWP
=
f
FWP
: Frequency at field weakening point;
U
Nmains
: Input power voltage;
U
Nmotor
: Rated motor voltage;
f
Nmotor
: Rated motor frequency
Scalar Control mode (not for ACP 600): 0 to 300 Hz
With dv/dt Filter (DTC and Scalar Control modes): 0 to 120 Hz
Frequency Resolution: 0.01 Hz
Current: see rating tables
Power Limit: 1.5 ·
P
hd
Overcurrent Trip: 3.5 ·
I
2hd
Field Weakening Point: 8 to 300 Hz
Switching Frequency: 3 kHz (average). In 690 V units 2 kHz
(average).
Maximum Recommended Motor Cable Length: 300 m (980 ft). This
is the cumulative length in case of parallel connected motors. For ACx
601-0005-3 to ACx 601-0016-3, ACx 601-0006-5 to ACx 601-0020-5,
ACx 601-0009-6 to ACx 601-0020-6, if the motor cable length exceeds
70 metres (230 ft), an ABB representative should be consulted.
Motors larger than 90 kW (125 HP) Motors: Insulated bearing at non-
driven end is recommended.
U
Nmains
U
Nmotor
·
f
Nmotor

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS 604 and is the answer not in the manual?

ABB ACS 604 Specifications

General IconGeneral
BrandABB
ModelACS 604
CategoryController
LanguageEnglish

Related product manuals