Appendix A – ACS/ACC/ACP 604/607 Technical Data
ACS/ACC/ACP 604/607 Drives ACx=ACS/ACC/ACP A-29
Public Low-Voltage
Network
1. The ACx 600 is equipped with EMC filtering (refer to Table A-1).
2. The ACx 607 is installed with motor and control cables as specified in this manual
(for types ACS/ACC 607-0400-3, -0490-3/5/6, -0610-3/5/6 and -0760-5/6 with
power cables as specified in
ACS 600 Power Extension Range Supplement
).
3. Maximum cable length is 100 metres.
Without considering the EMC requirements, do not use the ACx 600 on a low voltage
public network supplying domestic premises. This kind of use might cause radio
frequency interference.
Ungrounded Power Lines
(IT Network)
1. It is ensured that no excessive emission is propagated to neighboring low-voltage
networks. In some cases, the natural suppression in transformers and cables is
sufficient. If in doubt, the supply transformer with static shielding between the
primary and secondary windings can be used.
2. The ACx 607 is installed with motor and control cables as specified in this manual
(for types ACS/ACC 607-0400-3, -0490-3/5/6, -0610-3/5/6 and -0760-5/6 with
power cables as specified in
ACS 600 Power Extension Range Supplement
).
Note:
The ACx 600 must not be equipped with EMC filtering (refer to Table A-1) when
installed to floating networks. The power line becomes connected to ground potential
through the EMC filter capacitors. In floating networks this may cause danger or
damage the unit.
Machinery Directive
ACx 601/604/607 drives comply with the European Union Machinery Directive (89/392/
EEC) requirements for an equipment intended to be incorporated into machinery.