Appendix A – ACS/ACC/ACP 604/607 Technical Data
A-18 ACx=ACS/ACC/ACP ACS/ACC/ACP 604/607 Drives
Enclosures, Space
Requirements
The cabinets, degrees of protection and free space requirements of
ACx 600 types are given below.
1) ACx 604-0100-3, -0120-3, -0120-5, -0140-5, -0100-6, -0120-6
2)
ACx 604-0140-3 to -0320-3 & -0170-5 to -0400-5, -0140-6 to -0400-6
3)
not for frame sizes 2xR8 and 2xR9
4)
The degrees of protection is specified by listing the IEC standard IP (Ingress Protection) number. The first digit of the IP number specifies
the protection against solid objects and dirt. The second digit specifies the protection against liquids. IP 00 is an open chassis. NEMA 1
enclosures are comparable to approximately IP 20 to IP 33. NEMA 3R enclosures are comparable to IP 32. NEMA 12 and NEMA 13
enclosures are comparable to IP 54 to IP 65. NEMA 4 enclosures are comparable to IP 65 or IP 66.
ACx 600 Type Enclosure Degree of
Protection
5)
Space above
Space below
Space on
left/right
Space in
front/back
mm in mm in mm in mm in
604
2)
frame R7 IP 22 300 12 300 12 50/50 2/2 20/0 0.8/0
604
3)
frames R8 and R9 IP 00 400 16 0 0 0/50 0/2 100/0 4/0
607 Drives-MNS cabinet
IP 21
4)
/22
IP 42/54
200 8 0 0 0 0 200/0 8/0
First digit of IP number (protection against solid objects) Second digit of IP number (protection against liquids)
0 Not protected Not protected
1 Protected against solid objects larger than 50 mm (2 in.) dia. Protected against dripping water
2 Protected against solid objects larger than 12 mm (1/2 in.) dia. Protected against downward sprays of water up to 15 degrees
from vertical.
3 Protected against solid objects larger than 2.5 mm (0.1 in.) dia. Protected against downward sprays of water up to 60 degrees
from vertical.
4 Protected against solid objects larger than 1.0 mm (0.04 in.) dia. Protected against light sprays or splashing water from all
directions - water shall not enter the enclosure in harmful
quantities.
5 Dust protected - dust shall not enter the enclosure in sufficient
quantity to interfere with satisfactory operation of equipment.
Protected against low pressure sprays of water from all directions
- water shall not enter the enclosure in harmful quantities.
6 Dust tight Protected against heavy seas on shipdecks or strong sprays of
water from all directions - water shall not enter the enclosure in
harmful quantities.
Space requirement for the door opening
700 mm (27.6 in.) (2 x R8 and 2 x R9)
800 mm (31.5 in.) (R7, R8 and R9)