Appendix A – ACS/ACC/ACP 604/607 Technical Data
A-12 ACx=ACS/ACC/ACP ACS/ACC/ACP 604/607 Drives
Optional Terminal Block
X2
External connections to optional terminal block X2 for ACS 600
Standard Application Program (Factory Macro) are shown below.
External control connections are different with other application macros
and programs (see
Firmware Manual
).
.
ACS 607 I/O Interface
(optional)
ACS 601/604/607
NIOC Board
(A2)
Programmable I/O
Factory Settings
X2 X21
1 -------- 1 VREF Reference voltage
10 V d.c.
1 kΩ <
R
L
< 10 kΩ
2 -------- 2 GND
3 -------- 3 AI1+ Speed reference
0(2)... 10 V
R
in
> 200 kΩ
4 -------- 4 AI1-
5 -------- 5 AI2+ By default, not in use.
0(4)... 20 mA
, R
in
= 100 Ω
6 -------- 6 AI2-
7 -------- 7 AI3+ By default, not in use.
0(4)... 20 mA
, R
in
= 100 Ω
8 -------- 8 AI3-
9 -------- 9 AO1+ Motor speed 0(4)...20 mA
0...motor nom. speed,
R
L
< 700 Ω
10 -------- 10 AO1-
11 -------- 11 AO2+ Output current
0(4)...20 mA
0...motor nom. current,
R
L
< 700 Ω
12 -------- 12 AO2-
X22
13 -------- 1 DI1 Stop/Start
14 -------- 2 DI2 Forward/Reverse
1)
15 -------- 3 DI3 Not used
16 -------- 4 DI4 ACCEL/DECEL 1/2
17 -------- 5 DI5 Constant speed select
2)
18 -------- 6 DI6 Constant speed select
2)
19 -------- 7 +24V +24 V d.c. max. 100 mA
20 -------- 8 +24V
21 -------- 9 DGND Digital Ground
X23
22 -------- 1 +24 V Auxiliary voltage output, non-
isolated, 24 V d.c. 250 mA
23 -------- 2 GND
X25
24 -------- 1 RO11
Relay output 1
Ready
25 -------- 2 RO12
26 -------- 3 RO13
X26
27 -------- 1 RO21
Relay output 2
Running
28 -------- 2 RO22
29 -------- 3 RO23
X27
30 -------- 1 RO31
Relay output 3
Fault (-1)
31 -------- 2 RO32
32 -------- 3 RO33
=
=
Terminal Block Size
X21, X22, X23, X25, X26, X27:
cables 0.5 to 1.5 mm
2
(#20 to #16 AWG)
X2: cables 0.5 to 2.5 mm
2
(#20 to #14 AWG)
Control Cable Lead-through Size:
Ø: 2 x 3x2...11 mm (0.08 to 0.43”)
Factory settings of application software
selection B (type code):
DI1: Start, DI2: Stop, DI3: Reverse,
DI4: Acc/Dec 2,
DI5,6: Constant speed 1 to 3 select.
1)
Parameter 10.3 must be set to REQUEST.
2)
Operation: 0 = Open, 1 = Closed
Connector X28 for RS 485 connection
Connector X29 for RS 485 connection
DI 5 DI 6 Output
0 0 Set speed through AI 1
1 0 Constant Speed 1
0 1 Constant Speed 2
1 1 Constant Speed 3
1 TRANS
Panel Link Connections
2GND
3B-
4A+
5GND
Power to Remote Panel
6 +24V
1 TRANS
Panel Link Connections
2FAULT
3B-
4A+
5 GND Power to Panel
Fault
A
rpm