Appendix A – ACS/ACC/ACP 604/607 Technical Data
ACS/ACC/ACP 604/607 Drives ACx=ACS/ACC/ACP A-19
Cooling Air Flow
Requirements
Cooling air flow requirements are given below.
Heat DIssipation
Requirements
ACx 607 drives are self-cooled. The table below gives the heat
dissipated into the hot air exhausted from the drives. If the drives are
installed in a confined space, the heat must be removed from the area
by ventilation or air conditioning equipment.
ACx 60x
60x = 604/607
Flow
m
3
/h
h
3
/m
ACx 60x-0100-3/0120-5/0100-6 660 390
ACx 60x-0120-3/0140-5/0120-6 660 390
ACx 60x-0140-3/0170-5/0140-6/0170-6 1640 1000
ACx 60x-0170-3/0210-5/0210-6 1640 1000
ACx 60x-0210-3/0260-5/0260-6 1640 1000
ACx 60x-0260-3/0320-5/0320-6 1840 1100
ACx 60x-0320-3/0400-5/0400-6 1840 1100
ACx 607-0400-3/0490-5/0490-6 3580 2100
ACx 607-0490-3/0610-5/0610-6 3980 2300
ACx 607-0610-3/0760-5/0760-6 3980 2300
ACx 607 Type
Heat Dissipation
Watts BTU/Hr
ACx 607-0100 3000 10200
ACx 607-0120 3600 12300
ACx 607-0140 4200 14300
ACx 607-0170 5100 17400
ACx 607-0210 6300 21500
ACx 607-0260 7800 26600
ACx 607-0320 9600 32800
ACx 607-0400 12000 40900
ACx 607-0490 14700 50200
ACx 607-0610 18300 62400
ACx607-0760 22800 77800