Chapter 4 – Programming the AC 80
4-6 AC 80 User’s Manual
Essential Settings for
ACS 600 Standard Drive
Note that only the user-adjustable settings are represented here.
DRIDS
DRISTD
Base part:
Defining the value of POSITION:
Reference part:
NAME Max. 20 characters, e.g. dataset_StdDrive
ACT 1
DS_NO Dataset number (1 or 3)
WR_ENA 1 (Must be forced by a connection from the PC section)
NAME Max. 20 characters, e.g. STD_DR_OP_MODULEBUS
POSITION 100 + address of the drive. See below.
IMPL 1
TYPE ACS 600 STD
Position on
Optical
ModuleBus
Setting of drive
parameter 70.01
DRISTD POSITION setting
(100 × Cluster + Position)
117 101
218 102
319 103
• • • • • • • • •
12 28 112
REF1 Max. 20 characters, e.g. dataset_Standard_DR
REF2 Max. 20 characters