4-32 AC 80 User’s Manual
Essential Settings
Only the user-adjustable settings are represented. For more details,
see the
AC 80 PC Elements Reference Manual.
PM825
AF 100 part:
DSP
Base part:
Value references:
DAT
See the
AC 80 PC Elements Reference Manual.
CABLE S (Single) or R (Redundant).
EN_DTMO Enable Double Timeout:
NO; YES
TIMESYNC Time Synchronisation:
NONE; MASTER; SLAVE
BUSNO 0
STNNO 1…79 (Must match AC 80 hardware address setting).
NAME Unique dataset name (max. 20 characters).
ACT 0 = Spare element
1 = Active element
BUS 0
IDENT Dataset identification (1…50). Must match the IDENT
terminal value in the corresponding PC element.
SOURCE Direction of communication:
RECEIVE; SEND
STATION AF 100 station number of the opposite target.
CYCLETIM Transmission interval in milliseconds.
SORT_REF Sort references:
NO; YES
REF1 User-definable name of a DAT element.
REF2 User-definable name of a DAT element.
• • • • • •
REF8 User-definable name of a DAT element.