AC 80 User’s Manual 4-37
Figure 4-34 The IORX PC element.
Essential Settings
IORX
NCBIO1
Activation
The IORX element starts to send datasets when the value of terminal
WRx is 1.
C1 (Call Parameter) Block number (1 to 8).
C2 (Call Parameter) Number of datasets (1 to 2).
(Note: 1 recommended for NDSC)
C3 (Call Parameter) Data type (I or IL).
(Note: I only for NDSC)
NODE Node number (1 to 8).
EN 1
RESET 0
CNTRL See the
AC 80 PC Elements Reference Manual.
DS1 Dataset number (1 to 254).
(Note: 10 to 32 for NDSC)
WR1 1
I11 Transmit integer or long integer.
I21 Transmit integer or long integer.
I31 Transmit integer or long integer.
IOTYPE1 NO_DEVICE; DI/DO_DEVICE; AI/AO_DEVICE;
COUNTER_DEVICE; DSU_DEVICE
IOTYPE2 NO_DEVICE; DI/DO_DEVICE; AI/AO_DEVICE;
COUNTER_DEVICE; DSU_DEVICE
• • • • • •
IOTYPE12 NO_DEVICE; DI/DO_DEVICE; AI/AO_DEVICE;
COUNTER_DEVICE; DSU_DEVICE
IORX(C1,C2,C3)
NODE
EN ERR
RESET RDY
CNTRL LINK
DS1
WR1
I11 O11
I21 O21
I31 O31
ERRC

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB Advant Controller 80 and is the answer not in the manual?

ABB Advant Controller 80 Specifications

General IconGeneral
BrandABB
ModelAdvant Controller 80
CategoryController
LanguageEnglish

Related product manuals