AC 80 User’s Manual 4-33
AFTRA/MB90TRA
AFREC/MB90REC
Activation
The AF 100 part of the PM825 database element does not need
activation.
The Base part of the DSP element is activated by setting the ACT
terminal to 1.
The DAT elements do not need activation.
The AFTRA, AFREC, MB90TRA and MB90REC elements are
activated by setting the ACT terminal to 1.
Testing
The PM825 element has a WARNING terminal for non-fatal errors and
an ERR (Error) terminal for fatal errors.
The Base part of the DSP element has an ERR terminal for fatal errors.
The AFTRA, AFREC, MB90TRA and MB90REC elements have two
status output terminals, ERR and ERRC. These terminals indicate a
fatal error and the error code respectively.
IDENT Dataset identification (1…50).
SCAN Transmission interval in milliseconds (1…4096).
ACT 1
IDENT Dataset identification (1…50).
STATION Node number of the transmitter (1…79).
ACT 1