Chapter 4 – Programming the AC 80
4-8 AC 80 User’s Manual
DRIENG is used for addressing the drive, reading basic information
from it, and connecting the DB elements (DRIDS and DRIENG) of the
drive together.
Figure 4-4 Settings of the DB element DRIENG.
The DRIENG element has three different parts: Base, Parameter and
Reference parts.
The Base part has terminals for drive position (i.e. address on the
Optical ModuleBus) and drive type specification. The drive position
setting corresponds to drive parameter 70.01.
The Parameter part is used for reading basic information from the
drive.
The Reference part is used for specifying the DRIDS elements that are
to be used with the DRIENG element.
All output terminals of the Base, Parameter and Reference parts can
be connected to the PC section of the application program and
measured there.